Description:

Full fire inspection done by Inspector John Bieg on 4/25/07. "B".

Outstanding Inspections

Case Number: T07FR00800
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
04/25/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Repair the ceiling located above the water heater. A re-inspection is scheduled for 5/9/07.
04/25/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag the fire extinguisher located by the register. #2. Service and tag both hood systems. #3. Service and tag the fire extinguisher located by the compressed gas cylinder against the south wall in the kitchen.
04/25/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean both hood systems in the kitchen. { Be sure to clean behind the cooking equipment.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00800
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/16/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 5/16/07.