Description:

Inspection

Outstanding Inspections

Case Number: T07FR00780
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/23/2007 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage at NW stockroom shall be 18 inches below sprinklers.
04/23/2007 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 508.5.4 Sprinkler control valves shall not be obstructed.
04/23/2007 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Clear space at electrical panels at west side equipment room.
04/23/2007 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4 Multiplug adapter at office.
04/23/2007 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Exit sign at west side of sales floor needs cover.
04/23/2007 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Extinguisher at west exit needs inspection.
04/23/2007 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 Extinguisher at west exit needs hanger.
04/23/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 Double swinging doors shall not have padlock at west side.
04/23/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 Sign shall be posted at front door.
04/23/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit signs at stockroom (X3) shall be repaired.
04/23/2007 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 Gas cylinder at front counter.