Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

04/21/2007

Applicant:

TUCSON SCHOOL DISTRICT NO 1

Description:

Routine Inspection

Outstanding Inspections

Case Number: T07FR00767
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
12/12/2006 VIOL - PRECAUTION AGAINST FIRE WCUMMING Correction Required In the mechanical room, the is combustible storage on top of the large electrical transformer. The electrical devices shall be kept free of combustibles either on or near them.
12/12/2006 VIOL - PRECAUTION AGAINST FIRE WCUMMING Correction Required The fire sprinkler riser was difficult to access due to storage of miscellaneous items. Fire sprinkler riser controls shall be visible and accessible at all times.
12/12/2006 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required The portable fire extinguishers shall be serviced annually.
12/12/2006 VIOL - MEANS OF EGRESS WCUMMING Correction Required One or more emergency light assemblies was found to be inoperative. Repair or replace as needed.
12/12/2006 VIOL - MEANS OF EGRESS WCUMMING Correction Required One or more exit signs was found to be inoperative when the test button was activated. Repair or replace as needed.
12/12/2006 VIOL - MEANS OF EGRESS WCUMMING Correction Required The exits off of the back of the stage were obstructed by storage. All required or marked exits and exitways shall be kept free of all obstructions at all times.