Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

04/21/2007

Applicant:

TUCSON SCHOOL DISTRICT NO 1

Description:

Routine Inspection

Outstanding Inspections

Case Number: T07FR00759
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
03/23/2007 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required Fire extinguishers were found to have been last tested and / or serviced in 2004. Portable fire extinguishers shall be serviced annually.
03/23/2007 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required One of the pressure gauges on the fire sprinkler riser is not operating properly. Repair or replace.
03/23/2007 VIOL - MEANS OF EGRESS WCUMMING Correction Required Both exits leading off of the back of the stage were obstructed by storage. Marked and required exits shall be clear of all obstructions at all times.
03/23/2007 VIOL - MEANS OF EGRESS WCUMMING Correction Required Several classrooms still had the old emergency exit signs above a window leading to the outside. These windows were to some degree not accessible because of the placement of furniture or storage.
03/23/2007 VIOL - MEANS OF EGRESS WCUMMING Correction Required Several emergency exit lights were found to be inoperative when the test button was activated. The standby batteries in these lights shall be repaired or replaced as needed.