Case: T07FR00741
Case Details
Entered Date:
04/18/2007
Applicant:
TANAGER COMPANY (THE)
Description:
Full Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00741
Case Description: INSPECTION
Total Completed Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2007 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | TFC 310.2 Smoking shall be prohibited in areas where flammable and combustible materials are stored or handled. A "NO SMOKING" sign shall be posted in these areas. (Warehouse) |
05/07/2007 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | TFC 703.1 Cover opening in ceiling. (Mikes's closet) |
05/07/2007 | VIOL - FIRE SERVICE FEATURES | DRAMIREZ | Approved | TFC 501.1 Provide directional sings to Riser Room.(Warehouse) |
05/07/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 901.6 Provide spare sprinkler wrench. |
05/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.5 Extension cords arto be used for temporary use only.(Warehouse) |
05/27/2008 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.6 Replace cover plates, (Mike's closet, LP office). (Warehouse) |
05/27/2008 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1011.1 Provide EXIT signs directing path of travel where EXIT is not readily visable. (Sales Dept.) |
05/27/2008 | INSP - FULL | DRAMIREZ | Approved |