Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/13/2007

Applicant:

HIGH POINT ASSOCIATES & HECHT MILTON TR

Description:

Full fire inspection done by Inspector John Bieg on 4/11/07. "A-2" / Restaurant.

Outstanding Inspections

Case Number: T07FR00715
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
04/13/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3.1 An approved sign shall be placed on the double doors leading to the electrical control room, located on the west side of the building. A re-inspection is scheduled for 4/25/07.
04/13/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4 Remove the cube adaptor located by the char broil grill on the south wall. { Replace with a fused power strip.}
04/13/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag all hood systems located in the kitchen. #2. Service and tag all extinguishers located in the kitchen and office. #3. Service and tag the sprinkler system.
04/13/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Maintain records of hood system cleanings on the premises.
04/13/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 #1. Mount the class K portable fire extinguisher. #2. Mount the portable fire extinguisher located in the office.
04/13/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the pad lock from the door by the fryer.
04/13/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Repair the emergency lighting Unit located in the register area on the north wall.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00715
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/02/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 5/2/07. Inspector John Bieg.