Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/11/2007

Applicant:

RIVERFRONT VILLAGE LLC

Description:

Full fire inspection done by Inspector John Bieg 4/11/07. "A-2" / Restaurant.

Outstanding Inspections

Case Number: T07FR00698
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
04/11/2007 VIOL - ADMINISTRATION JBURGE Correction Required TFC 107.1 #1. Repair the panic hardware on the exit door in the kitchen. #2. Repair the actuating arm for the panic hardware on the east exit door. { Don't paint the actuating arm for the panic hardware. }
04/11/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Remove all storage located in the water heater closet.
04/11/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
04/11/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Place an approved cover over the electrical outlet located in the water heater closet. A re-inspection is scheduled for 4/25/07.
04/11/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service, tag and mount the class K portable fire extinguisher located in the kitchen. #2. Service and tag both hood systems located in the kitchen. #3. Service, tag and mount the portable fire extinguisher located in the office.
04/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the keyed deadbolt from the exit door located in the kitchen.
04/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 The west exit / entrance shall comply with this code.
04/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.6 Remove the thumb-turn lock from the east exit door.
04/11/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.3.3 #1. Secure all compressed cylinders located in the kitchen. #2. Secure the compressed gas cylinder used to inflate balloons located in the northwest corner of the seating area.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00698
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/15/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 6/15/07. Inspector John Bieg.