Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/10/2007

Applicant:

GOLDEN SOUTHWEST FINANCIAL GROUP LTD

Description:

Full fire inspection done by Inspector John Bieg 4/10/07. "A-2" / Restaurant.

Outstanding Inspections

Case Number: T07FR00687
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
04/10/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Replace the missing sprinkler connection inlet cover located on the exterior of the building on the southeast side. #2. Service and tag all hood systems. #3. Service and tag the sprinkler system.
04/10/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.5 Comply with this code. A re-inspection is scheduled for 4/24/07.
04/10/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and maintain a record of cleanings for all hood systems.
04/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 #1. The southeast exit sign shall be illuminated. #2. The exit sign located above the exit door in the kitchen shall be illuminated.
04/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1023.6 The exit located in the kitchen shall unobstructed access to a public way.
04/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 #1. Repair the emergency lighting located in the lobby. #2. Repair the emergency lighting located in section 3. #3. Repair the emergency lighting located in the back service station. #4. Repair the emergency lighting located in section 5. #5. Repair the emergency lighting by the restrooms. #6. Repair the emergency lighting located by the meat room. #7. Repair the emergency lighting located by the dish washing station in the kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00687
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/31/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 5/30/07. Inspector John Bieg.