Case: T07FR00648
Case Details
Entered Date:
04/06/2007
Applicant:
ROGERS STEVE V
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T07FR00648
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
04/06/2007 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. Remove storage overlapping shelving at ceiling height. All other areas except up against wall - maintain 18 inches clearance to ceiling. |
04/06/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove extension cord located on south wall near cube adaptor. |
04/06/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | or emergencies. 605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. Remove 3 prong cube adaptor from south wall of kitchen. |
04/06/2007 | VIOL - FIRE RESIST.RATED CONST | NSPRENGE | Violation | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction shall be maintained. Replace ceiling tile that has been breached ( in storage room, right next to sprinkler head.) |
04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | 1105.3 Aircraft welding apparatus 906.2 General requirements. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Have your fire extinguishers inspected yearly and maintained. |
04/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | requirements where flammable or combustible liquids are limited in depth [0.25 inch (6 mm) or less]. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on hangers or brackets. Mount all three fire extinguishers on wall brackets. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00648
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2007 | COMPL - REINSPECTION | NSPRENGE | Approved | All noted hazards and code violations have been abated. |