Case: T07FR00630
Case Details
Entered Date:
04/05/2007
Applicant:
ALPHA HEATH ROGERS TRUST
Description:
Full fire inspection done by Inspector John Bieg 4/5/07. "A-2" / Resturante.
Outstanding Inspections
Case Number: T07FR00630
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 Addressing shall comply with this code. |
| 04/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1. Service and tag all fire extinguishers. #2. Service and tag all the hood systems located in the kitchen. { Submit plans to add 1 more nozzle to the hood system for the deep fat fryers.} |
| 04/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean and maintain a record of cleaning for the hood systems in the kitchen. { Be sure to clean the nozzles for the char broil cooking equipment.} A re-inspection is scheduled for 4/19/07. |
| 04/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1004.3 Comply with this code. |
| 04/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 #1. Remove the pad lock from the exterior door located in the kitchen by the deep fat fryers. #2. Remove the pad lock from the exit door in the kitchen. |
| 04/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 #1. The south exit sign shall be illuminated. #2. The east exit sign shall be fully illuminated. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00630
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 6/15/07. Inspector John Bieg. |