Full fire inspection done by Inspector John Bieg 4/5/07. "A-2" / Resturante.

Outstanding Inspections

Case Number: T07FR00629
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
04/05/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Remove all storage located in the water heater closet.
04/05/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Addressing shall comply with this code.
04/05/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking the electrical service equipment located in the kitchen by the exit.
04/05/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Remove the extension cord through the ceiling by the soda machine.
04/05/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag the hood system located in the kitchen. A re-inspection is scheduled for 4/19/07.
04/05/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.6 Remove storage from obstructing the class K fire extinguisher located by the exit in the kitchen.
04/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1004.3 Post the occupancy load, 95, on the sign by the east exit.
04/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 The exit sign located by the rear exit shall be illuminated . { In the kitchen.}
04/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 #1. Repair the emergency lighting unit located by the restrooms. The south light bulb does not work. #2. Repair the emergency lighting unit located on the ceiling west of the south exit door. #3. Repair the emergency lighting unit located in the kitchen above the heated cabinet.
04/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 Remove trash and boxes from obstructing the exit located in the kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00629
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/21/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 5/21/07. Inspector John Bieg.