Case: T07FR00608
Case Details
Entered Date:
03/30/2007
Applicant:
HULLINGER ROBERT D & LISA GAIL CP/RS
Description:
Inspection
Outstanding Inspections
Case Number: T07FR00608
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 220 cord at main panel at center shop. |
| 03/30/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 J- box at main panel, secure |
| 03/30/2007 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 J-box covers throughout |
| 03/30/2007 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 906.7 Hanger for extinguisher |
| 03/30/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 Hardware at door frame at north south bay exit. |
| 03/30/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 Hardware at west exit of repair garage area. |
| 03/30/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.3 Sign at north exit |
| 03/30/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Exit at west repair garage area. |
| 03/30/2007 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.1 Prohibited painting |
| 03/30/2007 | VIOL - MOTOR FUEL DISPENSING | TKNAPP | Correction Required | 2211.6 Extinguisher at repair area |
| 03/30/2007 | VIOL - FLAMMABLE LIQUIDS | TKNAPP | Correction Required | 3404.3.4.4 Cabinet for flammible liquids. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00608
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2007 | INSP - FULL | TKNAPP | Approved |