Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/28/2007

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full fire inspection done by Inspector John Bieg 3-28-07. "M"/Hardware store.

Outstanding Inspections

Case Number: T07FR00592
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
03/28/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Lower the signs located in the display area to comply with this code.
03/28/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 504.2 The exterior door located in the office shall comply with this code.
03/28/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 #1. Remove the yellow extension cord located in the outside yard. #2. Remove the extension cord used to power the cooler motor tester. A re-inspection is scheduled for 4-11-07.
03/28/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.9 Mount the fire extinguisher located by the east exit door at an approved height.
03/28/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1 An approved exit sign shall be provided for the outside yard exit gate.
03/28/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Remove the slide bolts fom the outside yard exit gate.
03/28/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.6 Remove all non compliant locking devices from the south and east exit doors.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00592
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/23/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 4/23/07. Inspector John Bieg.