Case: T07FR00584
Case Details
Entered Date:
03/27/2007
Applicant:
LANGFAN WILLIAM K TR
Description:
Full Fire Prevention Inspection conducted 3/27/07 initiated by Complaint L07# 2514 - T07FR00571 Mr. Litwin 327-1658; / Thuan Ly.
Outstanding Inspections
Case Number: T07FR00584
Case Status: SUSPNDED
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2007 | INSP - FULL | DGREENLE | Correction Required | Full Fire Prevention Inspection conducted Tue 3/21 as initiated by complaint L07# 2514, T07FR00571. Your Certificate of Occupancy is on file with the City of Tucson. You are required to post a copy of your C of O on the premesis. Copies of the permits regarding the address change and exit blockage shall also be kept on the premesis. A record of your sprinkler inspections shall be kept on the premesis for 3 years. Keep a copy of this report for your records. |
05/10/2007 | VIOL - FIRE SERVICE FEATURES | DGREENLE | Correction Required | TFC 510.1 - Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. _____ Provide approved signage identifying the sprinkler riser room. _____ Doors and locks shall be maintained and easily operated. |
05/10/2007 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Correction Required | TFC 703.1 - The required fire-resistance rating of fire-resistance-rated construction shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. _____ Replace missing ceiling tiles. |
05/15/2007 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Correction Required | 315.2.1 Ceiling clearance. Storage shall be maintained ... a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____ Storeroom |
05/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove all un-grounded, un-protected extension cords. _____ Plug approved power taps directly into outlets. _____ Remove all flexable electrical cords that go through ceiling. |
05/15/2007 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. TFC 102.6.1 - Inspection (Annually) 1. Sprinklers shall be inspected from the floor level annually. 2. Sprinklers shall be free of corrosion, foreign materials, paint and physical damage... Any sprinkler shall be replaced that is painted. _____ Sprinkler system inspection, tag and records _____ Sprinkler heads painted south exterior of building |
05/15/2007 | VIOL - MEANS OF EGRESS | DGREENLE | Correction Required | TFC 1013.4.1 - In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches (914 mm). Exception: Nonpublic aisles serving less than 50 people, and not required to be accessible by Chapter 11 of the International Building Code, need not exceed 28 inches in width. _____ maintain adequate aisle width throughout occupancy. |
08/23/2007 | INSP - REINSPECTION | BCOBB | Violation | Re-inspection done 8/22/2007, after taking case from Greenleaf. MA 30 requiring the immediate unlocking and unblocking of all 4 exits. [done before I left premises]. Also by Monday 8/27/2007 manager is requested to have exit signs installed and an appointment for sprinkler system to be tested. There are to be NO keyed locks or latched on the inside of any exit door. [Thumb turn locks done!] / Sprinkler test is done. / Extension cords removed. / Aisles still a problem at times./ |