Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/27/2007

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full fire Inspection done by Inspector John Bieg 3-27-07. "M"/Electronic sales.

Outstanding Inspections

Case Number: T07FR00583
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
03/27/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 504.2 The southwest exterior door shall comply with this code.
03/27/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
03/27/2007 VIOL - INT.FINISH, DEC. MATL'S JBURGE Correction Required TFC 803.1.3 Remove items from obstructing the notthwest exit.
03/27/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service, mount and tag the fire extinguishers located by the rear exit. A re-inspection is scheduled for 4-10-07.
03/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 The northwest exit shall comply with this code.
03/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 The northwest exit sign shall be fully illuminated.
03/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Repair the emergency lighting unit located by the northwest exit.
03/27/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.3.3 Secure the helium bottle located by the rear exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00583
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/08/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 5/8/07. Inspector John Bieg.