Case: T07FR00577
Case Details
Entered Date:
03/26/2007
Applicant:
TUCSON SPEEDWAY SQUARE LLC
Description:
FULL PREVENTION INSPECTION
Outstanding Inspections
Case Number: T07FR00577
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 03/27/2007 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Violation | 2003 IFC 315.2.1 CEILING CLEARANCE. 1) STROAGE SHALL BE MAINTAINED 24" OR MORE BELOW THE CEILILNG IN NONSPRINKLERED AREAS OF BUILDINGS. |
| 03/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2003 IFC 605.3 WORKING SPACE CLEARANCE. 1) CLEAR AREA AROUND ELECTRICAL PANELS AT LEAST 30 INCHES WIDE BY 36 INCHES DEEP. |
| 03/27/2007 | VIOL - FIRE RESIST.RATED CONST | MWAINWRI | Violation | 2003 IFC 703.1 FIRE RESISTIVE CONSTRUCTION SHALL BE MAINTAINED. 1) REPAIR HOLE IN CEILING IN STOCKROOM ON NW WALL. |
| 03/27/2007 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2003 IFC 1026.3 EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED. 1) EXIT SIGN OVER NE DOOR IN STOCK ROOM NEEDS TO BE REPAIRED. 2) EXIT SIGN OVER DOOR ON EAST SIDE NEEDS TO BE REPAIRED. |