Description:

UST Inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00532
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
03/20/2007 INSP - AST/UST JLANGEJA Approved Contacted Marco Mejia @ 271-4638. He is the owner of the property and the tanks have been out of service for 6 months. I explained that we would issue him a Temporary OOS permit that would be good for 1 year. At that time he would have to remove them, using a state certified contractor. I will provide him with a list of contractors from ADEQ. He asked if he could abandon in place. I explained that we only allow if under a structure and would compromise stability if excavated.
03/21/2007 VIOL - FLAMMABLE LIQUIDS JLANGEJA Approved IFC 3404.2.13.1.2- Out of service for 90 days. Underground tanks not used for a period of 90 days shall be safeguarded in accordance with all the following or be removed in accordance with Section 3404.2.14: 1. Flammable or combustible liquids shall be removed from the tank. 2. All piping, including fill line, gauge opening, vapor return and pump connection, shall be capped or plugged and secured from tampering. 3. Vent lines shall remain open and be maintained in accordance with Sections 3404.2.7.3 and 3404.2.7.4. Removall instructions can be found at this website: www.ci.tucson.az.us/fire_prevention/Resources/USTRemove.doc
07/16/2008 INSP - REINSPECTION CFUNKE Approved Pre-citation issued. Certified mail.