Case: T07FR00531
Case Details
Entered Date:
03/20/2007
Applicant:
GOODWILL INDUSTRIES OF SOUTHERN
Description:
Full Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00531
Case Description: INSPECTION
Total Completed Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2007 | VIOL - PRECAUTION AGAINST FIRE | DRAMIREZ | Approved | TFC 315.2.1 Storage shall be maintained a minimum of 18" below sprinkler head deflectors. |
| 04/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.4.2 Re-locatable power taps shall be directly connected to a permanantly installed receptacle. (No piggy-backing) |
| 04/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.5 Extension cords shall not be a substitute for permanent wiring. |
| 04/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 901.6.1 Sprinkler deflectors shall be maintained free from build up. (i.e. dust, grease) |
| 04/05/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1027.3 Shall remove containers obstructing exit and receiving area. |
| 04/05/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1008.1.8 Rear exit door shall be provided with thumb turn lock. |
| 04/05/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1006.3 Emergency back up lighting shall be repaired. |
| 04/05/2007 | VIOL - FIRE SERVICE FEATURES | DRAMIREZ | Approved | TFC 510.1 Door to room containing automatic sprinkler riser shall be labelled "Riser Room". |
| 04/05/2007 | VIOL - FIRE SERVICE FEATURES | DRAMIREZ | Approved | TFC 505.1 Shall provide address numbers for the building. |
| 04/05/2007 | INSP - FULL | DRAMIREZ | Approved |