Full Inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00531
Case Description: INSPECTION
Total Completed Inspections - 10
End Date Description Inspector Results Comments
04/05/2007 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 315.2.1 Storage shall be maintained a minimum of 18" below sprinkler head deflectors.
04/05/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.4.2 Re-locatable power taps shall be directly connected to a permanantly installed receptacle. (No piggy-backing)
04/05/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.5 Extension cords shall not be a substitute for permanent wiring.
04/05/2007 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 901.6.1 Sprinkler deflectors shall be maintained free from build up. (i.e. dust, grease)
04/05/2007 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1027.3 Shall remove containers obstructing exit and receiving area.
04/05/2007 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1008.1.8 Rear exit door shall be provided with thumb turn lock.
04/05/2007 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1006.3 Emergency back up lighting shall be repaired.
04/05/2007 VIOL - FIRE SERVICE FEATURES DRAMIREZ Approved TFC 510.1 Door to room containing automatic sprinkler riser shall be labelled "Riser Room".
04/05/2007 VIOL - FIRE SERVICE FEATURES DRAMIREZ Approved TFC 505.1 Shall provide address numbers for the building.
04/05/2007 INSP - FULL DRAMIREZ Approved