Case: T07FR00530
Case Details
Entered Date:
03/20/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by inspector John Bieg 3-19-07.
Outstanding Inspections
Case Number: T07FR00530
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service equipment located in the back room. |
03/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 An approved cover shall be placed on the junction box located in the back room high on the wall. |
03/20/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 The sprinkler head located in the employee restroom shll be repaired to ensure the proper water pattern if activated. A re-inspection is scheduled for 4-3-07. |
03/20/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 Repair the emergency lighting located by the rear exit. |
03/20/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.2 Remove storage from obstructing the rear exit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00530
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 4/13/07. Inspector John Bieg. |