Description:

Full fire inspection done by inspector John Bieg 3-19-07.

Outstanding Inspections

Case Number: T07FR00530
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
03/20/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking the electrical service equipment located in the back room.
03/20/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 An approved cover shall be placed on the junction box located in the back room high on the wall.
03/20/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 The sprinkler head located in the employee restroom shll be repaired to ensure the proper water pattern if activated. A re-inspection is scheduled for 4-3-07.
03/20/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Repair the emergency lighting located by the rear exit.
03/20/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 Remove storage from obstructing the rear exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00530
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/18/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 4/13/07. Inspector John Bieg.