Case: T07FR00521
Case Details
Entered Date:
03/19/2007
Applicant:
JACQUES ROBERT
Description:
Full fire inspection done by Inspector John Bieg 3-19-07.
Outstanding Inspections
Case Number: T07FR00521
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. The back room shall comply with this code. 2. The meat case shall comply with this code. |
| 03/19/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 1. Remove the extension cord located through the ceiling by the office. 2.Remove the extension cord located by the northeast side beer cooler. If you have any questions call me at 791-4014 Ext.122. |
| 03/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. 1. Service and tag the fire extinguisher located in the mechanical room. |
| 03/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 1. Mount the fire extinguisher located by the southwest entrance to the produce storage area. |
| 03/19/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1. The southeast exit doors shall comply with this code. { Both doors shall be easily openable from the egress side.} |
| 03/19/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. 1. An approved exit sign shall be placed above the northwest exit door. |
| 03/19/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated. 1. The exit sign located above the southeast door to the back room shall be illuminated. |
| 03/19/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. 1. Remove all storage from blocking the northwest exit/entrance. |
| 03/19/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.3.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. 1. Secure the compressed cylinder bottles located in the mechanical room. |
Completed Inspections
Case Status: FIELD
Case Number: T07FR00521
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 4/23/07. Inspector John Bieg. |