Case: T07FR00485
Case Details
Entered Date:
03/15/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by inspector John Bieg 3-14-07.
Outstanding Inspections
Case Number: T07FR00485
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/15/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 The storage room and freezer shall comply with this code. A re-inspection is scheduled for 3-28-07. |
03/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service equipment located in the back room. |
03/15/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service and tag the fire extinguisher located in the back room. |
03/15/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.3.3 Secure the empty compressed gas cylinders located in the back room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00485
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 4/5/07. Inspector John Bieg. |