Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/13/2007

Applicant:

3200 N FIRST AVENUE LTD PARTNERSHIP

Description:

Full fire inspection done by Inspector John Bieg 3-12-07.

Outstanding Inspections

Case Number: T07FR00472
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
03/13/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Remove the cardboard and trash from around the deep fat freyer located in the bakery. A re-inspection is scheduled for 3-26-07.
03/13/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 #1.The electrical service equipment located in the basement shall comply with this code. #2. The electrical service equipment located in the bakery shall comply with this code.
03/13/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 #1. Remove the extension cord used to power the small mixer in the bakery. #2. Remove the extension cord used to power the Coke machine located by the bakery.
03/13/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 The outlet boxes with open wiring shall have approved covers.
03/13/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service and tag the fire extinguisher located in the basement.
03/13/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3. #1.The south west exit doors shall meet these requirements. # 2. The south east exit door shall meet these requirements.
03/13/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.9 Repair the actuating arm on the exit door, located by the roll-up in the dock area.
03/13/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 #1.The exit sign leading to the recieving dock shall be illuminated. #2.The exit sign located above the exit door, by the roll-up door, in the dock shall be illuminated. #3.The exit sign located on the wall by the produce and frozen meat section shall be illuminated. #4.The exit sign located above the north east exit shall be illuminated.
03/13/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.3.3 1.Secure the compressed gas cylinders located in the basement. 2.Secure the compressed gas cylinders located in the outside produce stock.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00472
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/04/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 4/4/07. Inspector John Bieg.