Case: T07FR00465
Case Details
Entered Date:
03/12/2007
Applicant:
DINO RAMIREZ
Description:
Full Inspection
Outstanding Inspections
Case Number: T07FR00465
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - LIFE SAFETY | None | Not Inspected |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00465
Case Description: INSPECTION
Total Completed Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2007 | VIOL - HAZARDOUS MATERIALS,GEN | DRAMIREZ | Approved | TFC 2703.4 MSDS (Material Safety Data Sheet) shall be readily available on the premises. |
| 02/20/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 906.2 Portable fire extinguishers shall be inspected annually. |
| 02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.5 Extension cords shall not be a substitute for permanant wiring. |
| 02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.6 Provide cover plates for all electrical outlet boxes. |
| 02/20/2007 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | TFC 703.1 Repair holes in walls and replace ceiling tiles. |
| 02/20/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1008.1.8.3 Provide sign over main exit door that reads "THIS DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED" |
| 02/20/2007 | INSP - FULL | DRAMIREZ | Approved |