Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

03/06/2007

Applicant:

ZONALPHA HOUSE CORPORATION

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T07FR00437
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
03/06/2007 INSP - FULL BCORRALE Correction Required On 3-6-07 a fire prevention inspection was conducted at 1501 N. Vine Av. Tucson, AZ. Please correct the following Tucson Fire Code violations. All code references are from the 2003 International Fire Code, with modifications.
03/06/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Violation 5.-Storage of combustibles in stairway.(All floors)
03/06/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Violation 6.-Storage of combustibles under stairs. 315.2.2 Means of egress. Combustible materials shall not be stored in exits or exit enclosures.2003 IFC **5.-Remove all storage in stairway, all floors. **6.-Remove all storage under stairway.
03/06/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Violation 7.-storage of mattresses on roof. 304.1.1 Waste material. Accumulations of wastepaper, wood, hay, straw, weeds, litter or combustible or flammable waste or rubbish of any type shall not be permitted to remain on a roof or in any court, yard, vacant lot, alley, parking lot, open space, or beneath a grandstand, bleacher, pier, wharf, manufactured home, recreational vehicle or other similar structure.2003 IFC **Remove mattresses from roof.
03/06/2007 VIOL - PRECAUTION AGAINST FIRE BCORRALE Violation 8.-Combustibles in mechanical room basement. 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms.2003 IFC **Remove combustibles in Mechanical room.
03/06/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Violation 10.-Extension cord in use in closet. 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.2003 IFC **Remove extension cord.
03/06/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Violation 9.-Electrical panel missing cover, needs a blank switch cover.(3rd floor) 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.2003 IFC **Install switch blank where needed, replace panel cover.
03/06/2007 VIOL - FIRE RESIST.RATED CONST BCORRALE Violation 3.-Ceiling tiles missing. Tile supports missing. -2nd floor -3rd floor
03/06/2007 VIOL - FIRE RESIST.RATED CONST BCORRALE Violation 4.-Stairway doors propped open with bricks, doorstops. 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.2003 IFC **3.-Replace ceiling tiles and associated support structures. **4.-Stairway doors shall remain closed at all times.
03/06/2007 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Violation 1.-Fire alarm system out of service.
03/06/2007 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Violation 2.-Fire alarm system due for testing. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.2003 IFC **1.-Repair alarm system immediately. Re-inspection on 3-7-07. **2.-Schedule system test.
03/06/2007 VIOL - MEANS OF EGRESS BCORRALE Violation 11.-Emergency lighting inoperative.(Laundry room) 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply.In the event of power supply failure, an emergency electrical system shall automatically illuminate area.2003 IFC **Repair lighting system.