AST Inspection

Outstanding Inspections

Case Number: T07FR00416
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
02/28/2007 INSP - AST/UST JLANGEJA Correction Required Temporary application of 1000 gallon AST for use of Class II liquid.
02/28/2007 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Violation IFC 2703.2.3- Equipment for storage of hazardous materials shall be listed or approved. Fitting on top of tank shall be replaced by a listed or approved part.
02/28/2007 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation IFC 3404.2.3.1- Signs shall be posted in storage areas prohibiting open flames and smoking. Signs stating "NO SMOKING" shall be posted within 25 feet of the tank.
02/28/2007 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation IFC 3404.2.3.2- Tanks greater than 100 gallons in capacity shall bear a label and placard identifying the materials therein. The tank shall be labeled with product name and bear a placard in accordance with NFPA 704.
02/28/2007 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation IFC 3404.2.7.3.3- Vent outlets shall be located such that flammable vapors will not be trapped by eaves The vent pipe shall be extended above the roof line and shall be secured against physical damage and vibration.
02/28/2007 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation IFC 3404.2.9.5.1.1- Aboveground tanks operating at pressures not exceeding 2.5 psig shall be located in accordance with Table 4.3.2.1.1 (a) of NFPA 30. The minimum distance from nearest side of any public way or from nearest important building on the same property shall be 5 feet.
02/28/2007 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation IFC 3404.2.9.6.5- Where aboveground tanks are subject to vehicular impact, they shall be protected by either using a UL2085 designed tank or meeting the provisions of Section 312, or both. The tank will need to be protected by bollards or concrete barriers that are approved for vehicle impact.
02/28/2007 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation IFC3404.2.12.2- Tanks shall be disposed in accordance with federal, state and local regulations. The 500 gallon AST shall be rinsed until there are no detectable vapors from fuel, or shall be purged and removed from site.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00416
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/22/2007 INSP - REINSPECTION JLANGEJA Approved Site inspection of property, all violations corrected. Inspection report approved, copies given to owner.