Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/27/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 2-23-07.

Outstanding Inspections

Case Number: T07FR00403
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
02/27/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 #1. Comply with this code in the areas of the office and stock room. #2. The flags located on the ceiling in the lounge area shall be a minimum of 18 inches from sprinkler head deflectors.
02/27/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking the electrical service equipment located in the stock room. A re-inspection is scheduled for 3-13-07.
02/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 #1. Repair emergency lighting located on the ceiling in the dudes dept. #2. Repair emergency lighting located on the ceiling in the betty's dept. #3. Repair emergency lighting that is mounted on the exit sign located in the office.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00403
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/29/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 3-28-07. Inspector John Bieg.