Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/27/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 2-23-07.

Outstanding Inspections

Case Number: T07FR00400
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
02/27/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking the electrical service equipment located in the office area.
02/27/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Remove the orange extension cord located by the west wall.
02/27/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 The electrical outlet located on the south wall next to the table shall have an approved cover.
02/27/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag , or replace the fire extinguisher located by the rear exit door. #2. Service and tag, or replace the fire extinguisher located by the exit door leading into the office. A re-inspection is scheduled for 3-13-07.
02/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 #1. The exit sign located above the rear exit door shall be illuminated. #2. The exit sign located above the exit door that leads to the exit access, in the office, shall be illuminated.
02/27/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.6 Remove the thumb turn deadbolt from the rear exit door.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00400
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/09/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 4/6/07. Inspector John Bieg.