Case: T07FR00400
Case Details
Entered Date:
02/27/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-23-07.
Outstanding Inspections
Case Number: T07FR00400
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service equipment located in the office area. |
02/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Remove the orange extension cord located by the west wall. |
02/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 The electrical outlet located on the south wall next to the table shall have an approved cover. |
02/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1. Service and tag , or replace the fire extinguisher located by the rear exit door. #2. Service and tag, or replace the fire extinguisher located by the exit door leading into the office. A re-inspection is scheduled for 3-13-07. |
02/27/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 #1. The exit sign located above the rear exit door shall be illuminated. #2. The exit sign located above the exit door that leads to the exit access, in the office, shall be illuminated. |
02/27/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.6 Remove the thumb turn deadbolt from the rear exit door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00400
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 4/6/07. Inspector John Bieg. |