Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

02/23/2007

Applicant:

VAIL SCHOOL DISTRICT NO 20

Description:

Routine Inspection

Outstanding Inspections

Case Number: T07FR00384
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
02/21/2007 VIOL - PRECAUTION AGAINST FIRE WCUMMING Correction Required 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. Storage on shelving in the Science Prep room is within 18" of a sprinkler head deflector.
02/21/2007 VIOL - FIRE RESIST.RATED CONST WCUMMING Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Two ceiling tiles in the MPR storage room are either out of place or missing entirely. These tiles shall be replaced maintaining a continous ceiling.
02/21/2007 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. The nozzle piping and nozzles have been moved so that they no longer provide the originally installed and designed coverage for the kitchen appliances. The appliances shall be reloacated and / or the nozzles readjusted for complete suppression coverage.
02/21/2007 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. Extinguishing system units shall be weighed and the required amount of agent verified. Stored pressure-type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals indicated by the manufacturer. The second commercial cooking hood extinguishing system was last tested April 2006. These systems shall be tested every 6 months.
02/21/2007 VIOL - HAZARDOUS MATERIALS,GEN WCUMMING Correction Required 2701.3.3.1 Properties of hazardous materials. The physical and health-hazard properties of hazardous materials on site shall be known and shall be made readily available to employees, neighbors and the fire code official. MSDS (Material Safety Data Sheets) shall be available at anytime either on site in a visible and readily known position or off site but readily retrievable.