Case: T07FR00382
Case Details
Entered Date:
02/23/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by inspector John Bieg 2-22-07.
Outstanding Inspections
Case Number: T07FR00382
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 903.3.3 The sprinkler head pattern shall not be obstructed by drywall. { Located on the ceiling in the office.} |
02/23/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.6 The extinguisher located behind the registers shall not be obstructed. |
02/23/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 #1. Repair emergency lighting unit located above men's jeans. #2. Repair emergency lighting unit located above zone 2 by fitting rooms. A re-inspection is scheduled for 3-8-07. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00382
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/15/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 3-14-07. Inspector John Bieg. |