Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/23/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 2-22-07.

Outstanding Inspections

Case Number: T07FR00377
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/23/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Remove the extension cord used to power the cash register.
02/23/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Place an approved cover on the un-covered electrical outlet.
02/23/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Replace the missing ceiling tile located in the back room. A re-inspection is scheduled for 3-8-07.
02/23/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 The east exit sign located above the entrance shall be illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00377
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/15/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 3-14-07. Inspector John Bieg.