Case: T07FR00375
Case Details
Entered Date:
02/22/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-21-07.
Outstanding Inspections
Case Number: T07FR00375
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/22/2007 | VIOL - ADMINISTRATION | JBURGE | Correction Required | TFC 107.1 Repair or remove the non-required exit sign located on the ceiling just inside the exit corridor. A re-inspection is scheduled for 3-7-07. |
02/22/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 The storage room shall comply with this code. |
02/22/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service equipment located in the storage room. |
02/22/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 The rear exit shall be illuminated. |
02/22/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 #1. The exit sign located above the main entrance shall have emergency back-up power. #2. The exit sign leading to the exit corridor shall have emergency back-up power. #3. The emergency lighting units (2), located on the ceiling by the entrance shall have back-up power. |
02/22/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.2 Remove storage from obstructing the rear exit access. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00375
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 4/4/07. Inspector John Bieg. |