Description:

Full fire inspection done by Inspector John Bieg 2-16-07.

Outstanding Inspections

Case Number: T07FR00352
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/20/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 The stock room shall comply with this code. A re-inapection is scheduled for 3-2-07.
02/20/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking the electrical service equipment located in the stock room.
02/20/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Repair the emergency lighting located on the wall by the men's cash wrap.
02/20/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 Remove storage from blocking the exit access located in the stock room.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00352
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/14/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 3-13-07. Inspector John Bieg.