Case: T07FR00352
Case Details
Entered Date:
02/20/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-16-07.
Outstanding Inspections
Case Number: T07FR00352
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 The stock room shall comply with this code. A re-inapection is scheduled for 3-2-07. |
02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service equipment located in the stock room. |
02/20/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 Repair the emergency lighting located on the wall by the men's cash wrap. |
02/20/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.2 Remove storage from blocking the exit access located in the stock room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00352
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 3-13-07. Inspector John Bieg. |