Case: T07FR00351
Case Details
Entered Date:
02/20/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-16-07.
Outstanding Inspections
Case Number: T07FR00351
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1 Over-head lighting located in both storage rooms shall have approved covers. A re-inspection is scheduled for 3-2-07. |
02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove the storage from blocking the electrical service equipment located in the east stock room. |
02/20/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 The electrical outlet box located in the room behind the register shall have an approved cover. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00351
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 3/23/07. Inspector John Bieg. |