Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/15/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 2-14-07.

Outstanding Inspections

Case Number: T07FR00340
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
02/15/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Repair the light hanging from the ceiling located in the dressing room.
02/15/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 #1. Replace missing ceiling tiles located in the break room. #2. Replace missing ceiling tiles located in the dressing room. A re-inspection is scheduled for 2-28-07.
02/15/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 The exit sign located in the stock room shall be illuminated.
02/15/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 The emergency lighting box located on the North wall in the storage room shall have emergency back-up power.
02/15/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 Remove storage from blocking the exit in the storage room.
02/15/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.6 Remove the thumb turn deadbolt from the rear exit door.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00340
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/13/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 3-12-07. Inspector John Bieg.