Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/15/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 2-14-07.

Outstanding Inspections

Case Number: T07FR00339
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/15/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 The rear storage room shall comply with this code.
02/15/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Replace the missing ceiling tiles in the back storage room. A re-inspection is scheduled for 2-28-07.
02/15/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 #1. The 2 exit signs over the main entrance shall be illuminated. #2. The exit sign above the storage entrance shall be illuminated. #3. The rear exit sign shall be illuminated.
02/15/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 Remove storage from blocking the exit access in the back room.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00339
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/15/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 3-14-07. Inspector John Bieg.