Case: T07FR00335
Case Details
Entered Date:
02/15/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-14-07.
Outstanding Inspections
Case Number: T07FR00335
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Maintain the 18 inches of clearance from sprinkler head deflectors in the stock room. A re-inspection is scheduled for 2-28-07. |
02/15/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service equipment located in the storage room. |
02/15/2007 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Replace missing ceiling tiles located in the stock room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00335
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 3-13-07. Inspector John Bieg. |