Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/15/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 2-14-07.

Outstanding Inspections

Case Number: T07FR00335
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
02/15/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Maintain the 18 inches of clearance from sprinkler head deflectors in the stock room. A re-inspection is scheduled for 2-28-07.
02/15/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking the electrical service equipment located in the storage room.
02/15/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Replace missing ceiling tiles located in the stock room.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00335
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/14/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 3-13-07. Inspector John Bieg.