Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/15/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 2-14-07.

Outstanding Inspections

Case Number: T07FR00334
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/15/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Multiplug adaptors shall be pluged directly to a permanently installed receptacle. {located in the office.}
02/15/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking the electrical service equipment located in the storage room. A re-inspection is scheduled for 2-28-07.
02/15/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 The rear exit sign shall be illuminated.
02/15/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Repair emergency lighting located on the south wall.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00334
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/12/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 3-9-07. Inspector John Bieg.