Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/13/2007

Applicant:

VANTAGE WEST CREDIT UNION

Description:

FPI to initiate SIP, resulting from request for inspector L07#2482 - T07FR00319

Outstanding Inspections

Case Number: T07FR00320
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
02/28/2007 INSP - FULL DGREENLE Correction Required Full Fire Prevention Inspection conducted 2/27/07.
03/19/2007 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Correction Required TFC 605.3 - Working space shall be maintained around electrical panels. TFC 605.3.1 - Doors into electrical service rooms shall be marked. TFC 605.4.1 - Power strips shall be polarized, grounded and equipped with ove-curent protection. TFC 605.4.2 - Power strips shall be plugged directly into wall.
03/19/2007 VIOL - FIRE RESIST.RATED CONST DGREENLE Correction Required TFC 703.1 - Openings in ceilings of electrical rooms shall be repaired. TFC 703.2 - Fire doors shall be maintained (in accordance with NFPA 80) in an operative condition (and)...shall not be blocked or obstructed.* * should this remain an ongoing problem, the fire code official is authorized to require signs be prominantly displayed near each fire door designed to be kept normally closed: "Fire Door - Keep Closed." (TFC 703.2.1)
04/27/2007 COMPLIANCE DGREENLE Correction Required All corrections OK 4/27/07. Occupancy is referred TFD's "Self Inspection Program."
04/27/2007 VIOL - MEANS OF EGRESS DGREENLE Correction Required TFC 1027.6 - Where panic and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door.