Case: T07FR00320
Case Details
Entered Date:
02/13/2007
Applicant:
VANTAGE WEST CREDIT UNION
Description:
FPI to initiate SIP, resulting from request for inspector L07#2482 - T07FR00319
Outstanding Inspections
Case Number: T07FR00320
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/28/2007 | INSP - FULL | DGREENLE | Correction Required | Full Fire Prevention Inspection conducted 2/27/07. |
03/19/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.3 - Working space shall be maintained around electrical panels. TFC 605.3.1 - Doors into electrical service rooms shall be marked. TFC 605.4.1 - Power strips shall be polarized, grounded and equipped with ove-curent protection. TFC 605.4.2 - Power strips shall be plugged directly into wall. |
03/19/2007 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Correction Required | TFC 703.1 - Openings in ceilings of electrical rooms shall be repaired. TFC 703.2 - Fire doors shall be maintained (in accordance with NFPA 80) in an operative condition (and)...shall not be blocked or obstructed.* * should this remain an ongoing problem, the fire code official is authorized to require signs be prominantly displayed near each fire door designed to be kept normally closed: "Fire Door - Keep Closed." (TFC 703.2.1) |
04/27/2007 | COMPLIANCE | DGREENLE | Correction Required | All corrections OK 4/27/07. Occupancy is referred TFD's "Self Inspection Program." |
04/27/2007 | VIOL - MEANS OF EGRESS | DGREENLE | Correction Required | TFC 1027.6 - Where panic and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door. |