Case Number: T07FR00317
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
02/13/2007 INSP - FULL BCORRALE Correction Required On 2-8-07 a fire prevention inspection was conducted at Offshore Group, 8350 E. Old Vail Rd. Please correct the following violations of the Tucson Fire Code. References are from the 2003 International Fire Code, with modifications.
02/14/2007 VIOL - EMERGENCY PLAN/PREPARE BCORRALE Violation 1. No Material Safety Data Sheets (MSDS) for Janitors' closet. 407.2 Material Safety Data Sheets. Material Safety Data Sheets MSDS) for all hazardous materials shall be readily available on the premises.TFC2003 ***Provide MSDS sheets on premises.
02/14/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Violation 2. Electrical panel blocked. 605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space.TFC2003 ***Unblock electrical panel.
02/14/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Violation 3. Extension cord used to power equipment.(secure room). 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ***Replace extention cord with UL approved power strip.
02/14/2007 VIOL - FIRE RESIST.RATED CONST BCORRALE Violation 4. Ceiling tiles missing, not seated. -Secure room -outside of breakroom 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.TFC2003 ***Replace/reseat ceiling tiles.
02/14/2007 VIOL - HAZARDOUS MATERIALS,GEN BCORRALE Violation 5. Indoor Propane storage neccessitates NFPA 704 placard on outside of building. 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. ***Install NFPA 704 placards outside of building where forklifts will be stored overnight.