Case: T07FR00299
Case Details
Entered Date:
02/08/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-7-07.
Outstanding Inspections
Case Number: T07FR00299
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Remove items from obstucting sprinkler heads and maintain a minimum of 18 inches of clearance from the ceiling. Call me if you have any questions at 791-4014, Ext.122. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00299
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 3-13-07. Inspector John Bieg. |