Case: T07FR00291
Case Details
Entered Date:
02/08/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-7-07.
Outstanding Inspections
Case Number: T07FR00291
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Remove storage from blocking sprinkler head deflectors in the storage room. A re-inspection is scheduled for 2-22-07. |
02/08/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service equipment in the storage room. |
02/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 Mount the extinguisher located in the rear storage room. |
02/08/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 #1. Exit sign over the front entrance shall have emergency back-up power. #2. Exit sign over the door leading into the exit corridor shall have emergency back-up power. #3. Emergency lighting above the rear exit shall have emergency back-up power. #4. Emergency lighting in the rear storage room shall have emergency back-up power. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00291
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 3-12-07. Inspector John Bieg. |