Case: T07FR00283
Case Details
Entered Date:
02/07/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspsection done by Inspector John Bieg 2-6-07.
Outstanding Inspections
Case Number: T07FR00283
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service equipment in the storage room. A re-inspection is scheduled for 2-21-07. |
02/07/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 Emergency lighting by the rear exit door shall have emergency back-up power. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00283
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/22/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 2-21-07. Inspector John Bieg. |