Case: T07FR00272
Case Details
Entered Date:
02/06/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-5-07.
Outstanding Inspections
Case Number: T07FR00272
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1 Fused power strips shall be directly connected to a permanently installed receptacle. In the back room by the desk. A re-inspection is scheduled for 2-20-07. |
02/06/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 Rear exit sign shall have emergency back-up power. |
02/06/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.3.3 Secure the compressed gas cylinder in the restroom. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00272
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/21/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 2-20-07. Inspector John Bieg. |