Case: T07FR00260
Case Details
Entered Date:
02/05/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-2-07.
Outstanding Inspections
Case Number: T07FR00260
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2007 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Replace the missing ceiling tiles in the back stock room. A re-inspection is scheduled for 2-16-07. |
02/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 The exit sign above the main entrance shall be illuminated. |
02/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 #1. All emergency lighting on the ceiling in the display area shall comply with this code. #2. All exit signs shall have emergency back-up power. #3. The emergency lighting in the back stock room shall comply with this code. |
02/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.6 Remove the door knob from the rear exit door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00260
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 2-23-07. Inspector John Bieg. |