Case: T07FR00259
Case Details
Entered Date:
02/05/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 2-2-07.
Outstanding Inspections
Case Number: T07FR00259
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service equipment in the rear stock room. |
02/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Remove the extension cord in the rear storage area, over the exit access. |
02/05/2007 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Replace the missing ceiling tile in the rear storage area. A re-inspection is scheduled for 2-16-07. |
02/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.2 Remove storage from blocking the exit and exit access. |
02/05/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.6 The door knob on the rear exit door shall be removed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00259
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 2-16-07. Inspector John Bieg. |