Description:

Full fire inspection done by Inspector John Bieg 2-1-07.

Outstanding Inspections

Case Number: T07FR00244
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/01/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Remove storage from obstructing sprinkler head deflectors in the rear stock room.
02/01/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space 1. Remove storage from blocking the electrical service equipment in the back stock room. If you have any questions call me at 791-4014, Ext.122.
02/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1. Remove the door knob from the rear exit door.
02/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. 1. Remove storage from blocking the rear exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00244
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/14/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 3-13-07. Inspector John Bieg.