Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/01/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 2-1-07.

Outstanding Inspections

Case Number: T07FR00243
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
02/01/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. 1. Remove storage from blocking the electrical service equipment in the west storage room.
02/01/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Maintenance. The required fire-resistance rating offire-resistance-rated construction (including walls, fire stops,shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replacedwhen damaged, altered, breached or penetrated. 1. The ceiling by the stock room entrance shall comply with this code. 2. Replace the missing ceiling tiles in the west stock room. 3. Replace missing ceiling tiles in the east stock room.
02/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 1. The fire extinguisher in the east stock room shall be mounted. If you have any questions call me at 791-4014, Ext.122
02/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. 1. Repair emergency lighting in the second stock room on the far west wall.
02/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated. 1. The rear exit sign, leading into the exit corridor behind the store, shall be illuminated. 2. The exit sign in the east stock room shall be illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00243
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/05/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 4/5/07. Inspector John Bieg.