Case: T07FR00240
Case Details
Entered Date:
02/01/2007
Applicant:
BAPS WEST-INC
Description:
per Capt Leon Sta 4 went to a roof fire on 1/28/07- this is a Hindu Temple, found temp set up for cooking and heating, stoves out of place, would like f/u fire inspection to check out inside.
Outstanding Inspections
Case Number: T07FR00240
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2007 | INSP - FULL | RDUARTE | Correction Required | Hindu Temple, roof fire on 01/28/07, requesting f/u fire inspection to check out inside. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00240
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1008.1.8 Screen door in kicthen shall be provided with thumb turn-lock |
| 02/05/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1006.3 Emergency back-up lighting shall be provided and maintained at all times. 1.) girls room ( burnt out) 2.) kitchen ( burnt, painted with over-spray) |
| 02/05/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1072.2 Exit signs shall be illuminated at all times. Every exit sign in the building shall be repaired. |
| 02/05/2007 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | TFC 703.1 Openings on ceiling or walls shall be protected from passage of smoke or fire. 1.) girls room (ceiling) 2.) chemical room (opening in wall) 3.) water heater room (ceiling and wall) 4.) riser room (ceiling) |
| 02/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.6 Cover plates shall be provided for outlet boxes. |
| 02/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.5 Extension cords shall not be a subtitute permanant wiring. |
| 02/05/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.3.1 Door to the elecrtrical room shall be labled, "ELACTRICAL ROOM" |
| 02/05/2007 | VIOL - FIRE SERVICE FEATURES | DRAMIREZ | Approved | TFC 505.1 Address numbers shall be visable from street. |
| 02/05/2007 | VIOL - FIRE SERVICE FEATURES | DRAMIREZ | Approved | TFC 510.1 Sprinkler riser room door shall be labled, "RISER ROOM" |
| 03/12/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 906.6 Sprinkler heads that have been oversprayed with paint shall be replaced. |