Case: T07FR00221
Case Details
Entered Date:
01/30/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 1-29-07.
Outstanding Inspections
Case Number: T07FR00221
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking electrical service equipment, in back room. A re-inspection is scheduled for 2-12-07. |
01/30/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 Emergency lighting by the restroom shall have back-up power. |
01/30/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.2 Remove storage from obstructing the required width of the exit. Rear exit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00221
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/21/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 2-20-07. Inspector John Bieg. |