Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/30/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 1-29-07.

Outstanding Inspections

Case Number: T07FR00217
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
01/30/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking electrical service equipment in the back room. A re-inspection is scheduled for 2-12-07.
01/30/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Replace broken ceiling tiles in the back room.
01/30/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.6 The fire extinguisher mounted on the wall by the rear exit shall not be obstructed.
01/30/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 The fire extinguisher on the floor by the rear exit shall be mounted.
01/30/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 #1. Exit sign over front door shall have emergency back-up power. #2. Rear exit sign shall emergency back-up power.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00217
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/21/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 2-20-07. Inspector John Bieg.